[1]陈旸羚,*,李维,等.输电钢管杆加挂通信天线后结构安全裕度评价[J].山东建筑大学学报,2020,(02):96-102.[doi:10.12077/sdjz.2020.02.014]
 CHEN Yangling,*,LI Wei,et al.Structural safety margin evaluation of transmission steel pipe towers with communication antennas[J].Journal of Shandong jianzhu university,2020,(02):96-102.[doi:10.12077/sdjz.2020.02.014]
点击复制

输电钢管杆加挂通信天线后结构安全裕度评价()
分享到:

《山东建筑大学学报》[ISSN:1673-7644/CN:37-1449/TU]

卷:
期数:
2020年02期
页码:
96-102
栏目:
研究论文
出版日期:
2020-04-15

文章信息/Info

Title:
Structural safety margin evaluation of transmission steel pipe towers with communication antennas
文章编号:
1673-7644(2020)02-0096-07
作者:
陈旸羚1*李维1吴桐2
(1.国网江苏省电力有限公司南京供电分公司,江苏 南京 210019;2.中通服咨询设计研究院有限公司,江苏 南京 210019)
Author(s):
CHEN Yangling1*LI Wei1WU Tong2
( 1. State Grid JiangSu Electric Power Co.,Ltd. Nanjing Supply Company, Nanjing 210019, China;2. China Information Consulting & Designing Institute Co., Ltd, Nanjing 210019, China )
关键词:
输电塔通信天线有限元分析安全裕度
Keywords:
transmission tower communication antenna finite element analysis safety margin
分类号:
TU476
DOI:
10.12077/sdjz.2020.02.014
文献标志码:
A
摘要:
运用结构安全裕度评价城市内加挂通信天线的输电杆塔,是解决现行输电杆塔结构校核周期长、成本高的有效途径。文章通过道亨满应力设计软件有限元建模分析了江苏省省网输电钢管杆2E2模块6种塔型,并对比加挂天线前后钢管杆的结构受力特性,提出了杆塔应力及挠度安全裕度风险评价方法。结果表明:省网2E2模块输电钢管杆具有加挂通信天线的可行性;其模块中初始安全裕度由高到低依次为终端塔、转角塔、直线塔,应优先选取终端塔或者转角塔作为加挂对象。
Abstract:
Using structural safety margin to evaluate transmission towers with communication antennas in cities is an effective way to solve the current long check cycle and high cost of transmission tower structures. In this article, six types of towers of Jiangsu Province State Grid steel pipe 2E2 module were analyzed by finite element modeling using Daoheng stress design software. The structural stress characteristics of steel poles before and after adding antennas are compared, and a risk assessment method of tower stress and safety margin for deflection is proposed. Through analysis, it is known that the transmission steel pipe tower loading the communication antenna are feasible; the initial safety margin in the 2E2 module is end tower, corner tower, and straight tower in order from high to low, the end tower or corner tower should be selected as the first target.

参考文献/References:

[1]冯翔,郭磊. 铁塔与通信行业资源共享的研究[J].江西电力,2019(6):24-26. [2]王毅,陈启鑫,张宁,等.5G通信与泛在电力物联网的融合:应用分析与研究展望[J].电网技术,2019,43(5):1575-1585. [3]陈旭奇.通信基础设施规划编制要点[J].电信快报,2018(7):26-29. [4]赵寅,李觐,干大成,等.针对公共社会资源的整合及使用的研究[J].通信与信息技术,2019(1):37-41. [5]龚婧,王永益,毛雨,等.紧凑型输电铁塔静力性能研究[J].水电能源科学,2011,29(12):167-169. [6]杨风利,杨婧波,韩军科,等.煤矿采空区基础变形特高压输电铁塔的承载力计算[J].中国电机工程学报,2009,29(1):100-106. [7]韩枫.特高压输电塔线体系的抗风可靠度研究[D].重庆:重庆大学,2012. [8]王飞,李正,杨风利,等.特高压酒杯型铁塔地震反应谱分析[J].高压电技术,2018,44(3):968-975. [9]王身丽,严利雄,陈典丽,等.输电线路杆塔受力分析研究现状[J].科技创新与应用,2018(35):71-72. [10]张宏杰,杨婧波,杨风利,等.台风风场参数对输电杆塔力学特性的影响[J].中国电力,2016,49(2):41-47. [11]张兆军.共享电力杆塔进行移动通信基站建设的实践总结[J].科技创新导报,2018,15(34):146-148. [12]DLT 5154—2012,架空输电线路杆塔结构设计技术规定[S].北京:中国计划出版社,2012. [13]DLT 5130—2001,架空送电线路钢管杆设计技术规定[S]. 北京:中国电力出版社,2001. [14]王伟煌.电力杆塔结构体系可靠度分析研究[J].机电信息,2015(6):140-141. [15]GB 50009—2012,建筑结构荷载规范[S].北京:中国建筑工业出版社,2012. [16]吕付玉,刘宏滨.道亨铁塔满应力分析软件与自立式铁塔内力分析软件的对比分析[J].广东电力,2011,24(6):31-34. [17]DL 5009.2—2013,电力建设安全工作规程 第2部分:电力线路[S].北京:中国电力出版社,2014. [18]杜志明,范军政.安全裕度研究与应用进展[J].中国安全科学学报,2004,14(6):6-10. [19]王燕,杜叶志,阮江军.高压架空输电线路覆冰情况下风险评估研究[J].电力系统保护与控制,2016,44(10):84-90.

备注/Memo

备注/Memo:
收稿日期:2020-03-09 基金项目:国网江苏省电力有限公司科技项目(J2019067)作者简介:陈旸羚(1984-),女,工程师,学士,主要从事电力无线专网等方面的研究.E-mail:448405204@qq.com[*通讯作者]
更新日期/Last Update: 2020-01-18